In Reply to: for those who built Signal DU/SU-based conditioners posted by rhyno on July 5, 2012 at 17:34:04:
For the DU-3 I would put a 10-15 amp fast-blo fuse in the PRIMARY of the transformer. Do NOT put fuses in the secondary because a soft fault might only blow one fuse leaving the whatever it's powering still energized with 60V.